The price of a degree-hour in data-centre cooling: auditing deep RL against model predictive control

Top story 7 in the issue of 24 October 2026, in 39 AI Cloud & Data Centres.

Original source

The price of a degree-hour in data-centre cooling: auditing deep RL against model predictive control

Benchmarks used to show reinforcement-learning savings put very different implied prices on overheating; checked against two metered tropical sites, the best RL policies traded comfort for energy far more cheaply than real plants would.

Evidence

Evidence: Peer-reviewed (evidence step 5 of 6)

Published after review by independent experts.

The story in three lines

Key finding
Learned policies accepted overheating at 40–42.7 kWh per degree-hour, versus 0.73–1.22 measured at real plants.
Significance
Technical: some reported AI cooling savings come from benchmark weights rather than better control.
Takeaway
Operators should test AI cooling against tuned classical controllers with realistic penalties.